Indah Rahmawati, Aripriharta, Irham Fadlika, Atika Rahmadani, Evie Dwi Jayanti, Gwo Jiun Horng
This paper presents an analysis of the impact of harmonic currents on overcurrent relay settings. In the case of a Steam Power Plant (PLTU) with an Electrostatic Precipitator (ESP) load, this can cause an increase in load current exceeding the overcurrent relay setting. As a result, overcurrent relays will trip. From the survey obtained TDD ESP PLTU data in each phase were obtained 4.75%, 5.16% and 5.02%, where phases B and C exceeded the limits in the IEEE standard. We have simulated using MATLAB / Simulink in two scenarios. Simulations with linear loads and nonlinear loads (ESP) to determine the impact of harmonics on the performance of overcurrent relays. The harmonic current source is modeled based on archived data. The simulation results show that the current relay arrangement is more ideal for the case of this study is 52506.75 A © 2019 IEEE.
Universitas Negeri Malang, Department of Electrical Engineering, Malang, Indonesia; Centre of Advanced Materials for Renewable Energy, Universitas Negeri Malang, Department of Electrical Engineering, Malang, Indonesia; Southern Taiwan University of Science and Technology, Department of Computer Science and Information Engineering, Tainan, Taiwan